Specifications of CP2101-9R

Input Voltage
48V
Screening Level
Commercial
Operating Temperature Min Deg. C
-40C
Operating Temperature Max Deg. C
71C
Product Length (mm)
164mm
Product Depth (mm)
111mm
Product Height (mm)
19.8mm
Mounting Style
Din-Rail
Pin Count
15
Number Of Outputs
2
Lead Free Status / RoHS Status
Not Compliant
Fig. 13
12 V tracking output V
V
Fig. 14
15 V tracking output V
Fig. 15
24 V tracking output V
Output Current Limitation
All outputs are continously protected against open-circuit (no
load) and short-circuit by an electronic current limitation.
Single- and double-output powertrains have a rectangular
BCD20010-G Rev AC, 26-Aug-09
o3
versus I
25 V
23 V
26 V
24 V
13 V
11 V
V
14 V
12 V
17 V
15 V
14 V
16 V
V
V
o3
o3
o3
or V
or V
0
0
0
or V
o3
o4
o4
(powertrain 2). V
o4
1
1
2
o
o
o4
2
®
= f(I
= f(I
versus I
o
o
2
4
), V
), V
3
i
i
i
= V
= V
= V
o4
4
(powertrain 1) or
i nom
i nom
i nom
3
6
5
4 A
3 A
2 A
1 A
8 A
6 A
4 A
2 A
6.5 A
4.7 A
3.2 A
1.6 A
4
8
6 A
A
A
I
I
I
o3
o3
o3
or I
or I
or I
o4
o4
o4
Page 13 of 25
current limitation characteristic. In double output power-
trains only the total current is limited allowing free choice of
load distribution between the two outputs of each power train
up to a total I
Thermal Considerations and Protection
If a converter is mounted upright in free air, allowing
unrestricted convection cooling, and is operated at its
nominal input voltage and output power at T
Temperature specifications), the temperature measured at
the measurement point on the case T
Data) will approach T
However the relationship between T
on the operating conditions and system integration. The
thermal conditions are influenced significantly by the input
voltage, the output current, airflow, and the temperature of the
adjacent elements and surfaces. T
to T
A temperature sensor fitted on the main PCB disables the
output, when the case temperature exceeds T
converter automatically resumes, when the temperature
drops below this limit. A temperature sensor on each power
train reduces the output current limit of that power train, when
the temperature exceeds a safe level.
Output Power at Reduced Temperature
Operating the converters with an output current between I
and I
temperature or forced air cooling in order to keep T
95 °C. When T
activated and disables the outputs.
Fig. 16
Output power derating versus T
Note: Forced cooling or an additional heat sink can improve the
reliability or allow T
exceeded. In rack systems without proper thermal management
the converters should not be packed too closely together! In such
cases the use of a 5 or 6 TE front panel is recommended.
C max
P
P
o max
o nom
o max
P
only an indicative value.
o
T
A min
90 – 194 Watt DC-DC Converters
o1
requires a reduction in maximum ambient
+ I
C max
50
o4
A
= I
to go beyond T
convection
cooling
is exceeded, the thermal protection is
o max
C max
60
or I
05117a
after an initial warm-up phase.
70
o2
P Series Data Sheet
+ I
A
A max
.
o3
80
cooling
A max
forced
A
= I
, provided that T
and T
o max
is therefore contrary
90
C
www.power-one.com
.
C
(see Mechanical
depends heavily
A max
°C
T
C max
C max
C max
T
(see table
A
C
is not
below
. The
o nom

Related parts for CP2101-9R