H5CX-L8-N AC100-240 Omron, H5CX-L8-N AC100-240 Datasheet - Page 7

RELAY TIMER DGTL SPDT 100/240VAC

H5CX-L8-N AC100-240

Manufacturer Part Number
H5CX-L8-N AC100-240
Description
RELAY TIMER DGTL SPDT 100/240VAC
Manufacturer
Omron
Series
H5CXr
Datasheets

Specifications of H5CX-L8-N AC100-240

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.001 Sec ~ 9999 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC
Mounting Type
Socket
Termination Style
8 Pin Socketable
Timing Adjustment Method
Up/Down Digit Keys
Timing Initiate Method
Input Voltage, Trigger Signal
Time Range
0.001s-9999hr
Power Consumption
6.2VA
Reset Time
20ms
Character Size
11.5mm
Time Range Min
0.001s
Supply Voltage Min
100VAC
Connector Type
8-Pin Socket
Signal Input Type
PNP/NPN
No. Of Digits / Alpha
4
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
PNP/NPN
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H5CXL8NAC100240
Z2999
Applicable Standards
*1. The following safety standards apply to models with sockets (H5CX-A11@ or H5CX-L8@).
*2. Excluding the H5CX-ASD-N/-A11SD-N/-L8SD-N.
I/O Functions
For details, refer to the timing charts on page 20 and page 29.
*1. The H5CX-L8E@ does not have an input.
*2. The H5CX-L@ does not have a gate input.
Response Delay Time When Resetting (Transistor Output)
The following table shows the delay from when the reset signal is input until the output is turned OFF.
Approved safety standards
EMC
Inputs
Outputs
cUL (Listing): Applicable when an OMRON P2CF (-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
Minimum reset signal width
*1
Start signal
Reset
Gate
Control output (OUT)
20 ms
1 ms
*2
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14
conforms to EN61812-1 (Pollution degree 2/overvoltage category III)
B300 PILOT DUTY
1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A resistive load
VDE0106/P100
CCC: Pollution degree 2, Overvoltage category II
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Immunity Surge:
Immunity Voltage Dip/Interruption:
Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing.
• Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time mode,
• Count inputs are not accepted and control output turns OFF while reset input is ON.
• Reset indicator is lit while reset input is ON.
Disables timing. (If a reset occurs while the gate input is ON, a reset will be performed.)
Outputs take place according to designated operating mode when timer reaches corresponding set value.
the present value returns to the set value.)
Output delay time
0.8 to 1.2 ms
15 to 25 ms
(Reference value)
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
EN61000-4-2: 6 kV contact discharge (level 2)
EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
EN61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3);
EN61000-4-5: 1 kV line to lines (power and output lines) (level 3);
EN61000-4-11: 0.5 cycle, 100% (rated voltage)
*2
8 kV air discharge (level 3)
10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3)
1 kV I/O signal-line (level 4)
2 kV line to ground (power and output lines) (level 3)
*1
,
H5CX-A@-N/-L@-N
7

Related parts for H5CX-L8-N AC100-240