2866598 Phoenix Contact, 2866598 Datasheet - Page 11

UPS 4A 12VDC

2866598

Manufacturer Part Number
2866598
Description
UPS 4A 12VDC
Manufacturer
Phoenix Contact
Series
Minir
Datasheets

Specifications of 2866598

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
48W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 4A
Size / Dimension
4.53" L x 2.66" W x 3.90" H (115mm x 67.5mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
48W
Efficiency
82%
Approvals
cUL, EN, UL, VDE
Output Voltage Rating
12 V
Number Of Outlets
1
Tower / Rackmount
DIN Rail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
104211_en_00
13
14
State
Supply voltage OK,
rechargeable battery is being
charged
Supply voltage OK,
rechargeable battery
charged (normal mode)
Buffer mode
Battery discharged, UBAT <
10.2 V DC
Rechargeable battery test
negative
Buffer time over and remote
shutdown activated
Output
Signaling
O U
0 ,5 1
3 0
t
2 0
T D
m a
x
m in
[
1 5
C
2
1 2
]
1 0
3
5
V 4
A
1 0
V D
I N
-1 6
C
A C
L (
+ )
Power In OK
LED on
LED on
LED off
LED off
LED on
LED off
1 0
0 -
N (
R 1
R e
P o
2 4
B a
- )
B a
w e
m o
t. -C
O v
0 V
O F
t. -M
r in
R 2
O N
A la
e rl
h a
t e
F
o d
rg e
O K
o a
rm
e
d
B a
t t e
r y
Signaling outputs
The connection is established through the "OUT DC 12 V, +,
–" screw connections. The set output voltage is 12 V DC at the
time of delivery. The output voltage from 10 V DC to 16 V DC
can be set on the potentiometer.
Signal outputs are connected using "Alarm", "Bat.-Mode" and
"Bat.-Charge" terminal blocks. Three control lamps and three
active switching outputs are provided for function monitoring.
Battery mode/ Battery
charge
LED is flashing; Battery
mode output: 0 V, Battery
charge: 12 V
LED off; Battery mode /
Battery charge output: 0 V
LED on; Battery mode
output: 12 V, Battery charge:
0 V
LED on; Battery mode /
Battery charge output: 0 V
LED off; Battery mode /
Battery charge output: 0 V
LED off; Battery mode /
Battery charge output: 0 V
CAUTION
Make sure that all output lines are dimensioned
according to the maximum output current or are
separately protected. The cables on the
secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
Alarm
LED off; output: 0 V
LED off; output: 0 V
LED off; output: 0 V
LED on; output: 12 V
LED on; output: 12 V
LED off; output: 0 V
MINI-DC-UPS/12DC/4