2866598 Phoenix Contact, 2866598 Datasheet - Page 5

UPS 4A 12VDC

2866598

Manufacturer Part Number
2866598
Description
UPS 4A 12VDC
Manufacturer
Phoenix Contact
Series
Minir
Datasheets

Specifications of 2866598

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
48W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 4A
Size / Dimension
4.53" L x 2.66" W x 3.90" H (115mm x 67.5mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
48W
Efficiency
82%
Approvals
cUL, EN, UL, VDE
Output Voltage Rating
12 V
Number Of Outlets
1
Tower / Rackmount
DIN Rail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
104211_en_00
Standards
Electrical Equipment for Machinery
Safety transformers for power supply units
Electrical safety (of information technology equipment)
Electronic equipment for use in electrical power installations
SELV
Safe isolation
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
Approvals
UL approvals
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge
Electromagnetic HF field
Fast transients (burst)
Surge current loads (surge)
Conducted interference
EN 61000-4-2
Housing
Contact discharge
Discharge in air
Comments
EN 61000-4-3
Housing
Frequency range
Field intensity
Comments
EN 61000-4-4
Input
Output
Signal
Comments
EN 61000-4-5
Input
Output
Signal
Comments
EN 61000-4-6
Input/Output/Signal
Frequency range
Voltage
Comments
EN 60950/VDE 0805 (SELV)
6 kV
Criterion B
10 V/m
2 kV (level 3 - asymmetrical: conductor to ground)
Criterion B
4 kV (level 4 - asymmetrical: conductor to ground)
10 kHz ... 80 MHz
Criterion A
EN 60204
EN 61558-2-17
EN 61558-2-17
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN VDE 0106-101
UL Listed UL 508
UL/C-UL Recognized UL 60950
Level 3
8 kV
Level 3
80 MHz ... 2 GHz
Criterion A
4 kV (level 4 - asymmetrical: conductor to ground)
1 kV (level 2 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
2 kV (Level 3 - asymmetrical)
1 kV (Level 3 - symmetrical)
2 kV (Level 3 - asymmetrical)
1 kV (Level 3 - symmetrical)
Criterion B
Level 3
10 V
MINI-DC-UPS/12DC/4
PHOENIX CONTACT
5

Related parts for 2866598