2866598 Phoenix Contact, 2866598 Datasheet - Page 13

UPS 4A 12VDC

2866598

Manufacturer Part Number
2866598
Description
UPS 4A 12VDC
Manufacturer
Phoenix Contact
Series
Minir
Datasheets

Specifications of 2866598

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
48W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 4A
Size / Dimension
4.53" L x 2.66" W x 3.90" H (115mm x 67.5mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
48W
Efficiency
82%
Approvals
cUL, EN, UL, VDE
Output Voltage Rating
12 V
Number Of Outlets
1
Tower / Rackmount
DIN Rail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
104211_en_00
17
Function
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
O U
0 ,5 1
3 0
t
T D
m a
2 0
x
[
m in
C
2
1 5
]
1 2
1 0
3
5
V 4
A
1 0
V D
I N
-1 6
C
A C
L (
+ )
1 0
0 -
N (
R 1
R e
B a
P o
2 4
- )
B a
m o
t. -C
w e
O v
0 V
t. -M
O F
O N
r in
R 2
A la
h a
e rl
t e
o d
o a
F
rm
rg e
O K
e
d
B a
t t e
r y
www.phoenixcontact.com
Setting the output voltage
In the normal mode, the output voltage of the device conforms
to the setting on the potentiometer (10 V DC ... 16 V DC). If the
supply voltage fails, the buffer mode is activated without any
interruption and the output voltage is supplied by the
rechargeable battery module. The output voltage is now
directly dependent on the battery voltage and is U
An alarm signal is triggered if the output voltage drops below
10.2 V in the buffer mode. If the output voltage drops to 9.6 V
due to a completely discharged rechargeable battery module,
the device switches off and remains switched off. The device
switches on automatically only after reconnecting the power
supply. The device is electronically protected against short-
circuits and no-load operation.
Buffer time setting
The buffer mode might be terminated after the preset time or
due to an external shutdown. If the device is to be shut down
after a specific time has elapsed, the time can be set via the
selector switch on the front of the device. The device can be
switched on in the buffer mode again after reconnecting the
power supply.
MINI-DC-UPS/12DC/4
BAT
- 0.5 V.
13

Related parts for 2866598