C200H-CN222 Omron, C200H-CN222 Datasheet - Page 115

no-image

C200H-CN222

Manufacturer Part Number
C200H-CN222
Description
CPM1A/CPM2A CABLE
Manufacturer
Omron
Datasheets

Specifications of C200H-CN222

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Specifications
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next trans-
mission cycle.
When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the trans-
mission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is trans-
mitted in the first transmission cycle when the B7A Link Terminal is turned on again.
Transmission errors between the C200H-B7A01 and B7A Link Terminal are detected by the B7A Link Terminal
only. Check the ERR indicator and error bit for any error.
Performance Specification
Note 1. The external power supply capacity does not include the capacity required by the B7A Link T erminal.
Function
Switch setting
Bit no.
allocation
Status of input indicator lamp 15
Status of the ERR indicator
I/O points
Transmission distance
Transmission delay
Minimum input time (see note 2)
Internal current consumption
External power supply (see note 1)
Weight
!
ll
Caution
2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit.
2. The minimum input time is the minimum time required to read input signals from the CPU. Be sure that
i
the ON/OFF width of signals sent to B7A Interface Unit output relays is at least 16 ms.
Input mode
If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be
damaged.
Item
00 to 14
15
Connection Terminals
SIG:
V–:
Input Mode Selector
The B7AI1 incorporates an input mode selector on the back panel of the Unit,
with which the following modes can be set.
Fifteen-point input from the B7A Link
Terminal is effective. Bit 15 is used as
transmission error bit.
Upper side
Input 00 to input 14
Transmission error bit
Not used
Lit when there is a transmission error and OFF during normal transmission
16 points or 15 points and 1 error
input
500 m max. if power is supplied to the Interface Unit and B7A Link Terminal
separately.
100 m max. if power is supplied to the Interface Unit and B7A Link Terminal
from a single power supply.
Typ. 19.2 ms, 31 ms max.
---
5 VDC, 100 mA max.
12 to 24 VDC ±10%, 10 mA min.
200 g max.
Connects to the SIG terminal of the B7A Link Terminal.
Connects to the negative power terminal of the B7A Link Terminal.
15 points + 1 error
C200H-B7AI1
Sixteen-point input from the B7A Link
Terminal is effective.
Lower side
Input 00 to input 14
Input 15
Lit when input 15 is ON. Not lit when
input 15 is OFF.
16 output points
16 ms
12 to 24 VDC ±10%, 30 mA min.
2
C200H-B7AO1
16 points
minimum.
Appendix B
101