CPM1A/CPM2A CABLE
Manufacturer
Omron
Datasheets

Specifications of C200H-CN222

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Output Leakage Current
Output Surge Current
Transistor Output
Residual Voltage
Wiring
If there is a possibility of leakage current causing a transistor or triac to malfunc-
tion, connect a bleeder resistor across the output as shown below.
Determine the value and rating for the bleeder resistor using the following for-
mula.
Where
E
I = leakage current in mA
R = bleeder resistance
When connecting a transistor or triac Output Unit to an output device having a
high surge current (such as an incandescent lamp), care must be taken to avoid
damage to the Output Unit. The transistor and triac Output Units are capable of
withstanding a surge current of ten times the rated current. If the surge current
for a particular device exceeds this amount, use the circuit shown below to pro-
tect the Output Unit.
Another way of protecting the Output Unit lets the load draw a small current
(about one third the rated current) while the output is OFF, significantly reducing
the surge current. This circuit (shown below) not only reduces the surge current,
but also reduces the voltage across the load at the same time.
When connecting TTL circuits to transistor Output Units, it is necessary to con-
nect a pull-up resistor and a CMOS IC between the two. This is because of the
residual voltage left on the transistor output after the output turns OFF.
on
= ON voltage of the load
PC
COM
COM
OUT
OUT
R
R
OUT
COM
R
Bleeder resistor
L
E
–––
on
I
L
R
L
Load power supply
Section
+
+