100-ms timer (delay timer for internal processing time of
Analog Output Unit)
Self-holding bit
Writes the parameter values of D00113 to D00118 to RAM
addresses 13 to 18 and, 100 ms later, turns ON the
Parameter Update Bit (bit 05 of word n+1).
Turns ON CIO 200003 when the Parameter Update Bit
turns ON (self-holding).
Sets #0001 in D00100.
Sets the value of D00201 in D00101.
Sets #0100 in D00198.
Increments the value of D00198 by 1 when the Analog
Output Unit Read Completed Flag (bit 06 of word n+3,
CIO 000506) turns OFF.
Compares the value of D00198 with #0101, and turns
ON CIO 200005 if they match (or data up to D00101 has
been written).
Writes the data memory value at the address
indicated by the value of D00198 to word n
(CIO 0002). (indirect address)
Sets the rightmost byte of D00198 in the leftmost byte of
word n+1 (CIO 0003).
Turns ON CIO 200201 to set the Read/Write Request Bit
to Write.
Turns ON CIO 200301 to turn ON the PC Write
Completed Bit.
Turns ON bit 00 of word n+1 (to set the Read/Write
Request Bit to Write) when CIO 200200 or CIO 200201
turns ON.
Turns ON bit 06 of word n+1 (PC Write Completed Bit)
when CIO 200300 or CIO 200301 turns ON.