C500DA101 Omron, C500DA101 Datasheet - Page 62

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Two-word Operation
46
(Continued on next page.)
(From previous page.)
07100
07101
07102
07001
07000
07001
00103
25506
07200
07201
07202
07203
07204
07205
07206
07207
(EQ)
MOV(21)
BCD(24)
BCD(24)
BCD(24)
BCD(24)
BCD(24)
BCD(24)
MOV(21)
MOV(21)
READ(88)
DM0108
DM0100
DM0300
DM0101
DM0301
DM0102
DM0302
DM0103
DM0303
DM0104
DM0304
DM0105
DM0305
DM0106
DM0306
DM0107
DM0307
DM0100
00008
00009
00010
07001
#0009
072
001
A/D converted data and the Disconnec-
tion Detect Flags from points 1 through 8
are read in and stored in DM 0100
through DM 0108. IR 00103 (the Uncon-
firmed Data Flag) stops unconfirmed data
from being accepted.
When reading is complete, SR
25506 (the Equal Flags) turns ON,
activating IR 07001.
Disconnection Detect Flags (the lower 8
bits of DM 0108) are output to IR 072.
Input point 1
Input point 2
Input point 3
Input point 4
Input point 5
Input point 6
Input point 7
Input point 8
Binary data from points
1 through 6 is converted
to BCD and written to
DM 0300 through DM
0305. IR 07200 through
07207 are used as work
bits activated by the Dis-
connection Detect Flags
to prevent data from be-
ing moved when an in-
put is disconnected.
Scaling (BCD output) is
performed on points 7
and 8 and the data is
written to DM 0306 and
DM 0307 without con-
version.
Section 4-3

Related parts for C500DA101