CS1W-BAT01 Omron, CS1W-BAT01 Datasheet - Page 23

no-image

CS1W-BAT01

Manufacturer Part Number
CS1W-BAT01
Description
"BATTERY,CPU,CS1 SERIES ONLY"
Manufacturer
Omron
Datasheets

Specifications of CS1W-BAT01

Rohs Compliant
YES
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Process and Analog I/O Units
Overview
A wide range of 25 I/O Units, including 16 Isolated-type Units, covers
almost all typical applications. Also featuring high-speed (10 ms) and
high-resolution (1/64,000) types, this line-up meets a diverse array of
potential uses, from data logging to high-speed measurement control.
Overview of Process Analog I/O Units
CS1W-PTS11
Isolated-type
Thermocouple Input
Unit (high-resolution)
Isolated-type
Resistance
Thermometer
Input Unit
(high-resolution)
Isolated-type DC Input
Unit (high-resolution)
Isolated-type Thermo-
couple Input Unit
(economical type)
Isolated-type
Resistance
Thermometer
Input Unit (economical
type)
Isolated-type
DC Input Unit
(economical type)
Isolated-type
Thermocouple Input
Unit
Isolated-type
Resistance
Thermometer
Input Unit
Isolated-type
Resistance
Thermometer
Input Unit (Ni508.4 Ω )
Process and Analog I/O Units
Name
CS1W-PTS11
CS1W-PTS12
CS1W-PDC11
CS1W-PTS51
CS1W-PTS55
CS1W-PTS52
CS1W-PTS56
CS1W-PDC55
CS1W-PTS01-V1
CS1W-PTS02
CS1W-PTS03
CS1W-PTS12
Model
4 inputs
4 inputs
4 inputs
4 inputs
8 inputs
4 inputs
8 inputs
8 inputs
4 inputs
4 inputs
4 inputs
Number of
I/O
CS1W-AD161
B, E, J, K, L, N, R, S,
T, U, WRe5-26, PLII,
± 100 mV
Pt100 Ω (JIS, IEC),
JPt100 Ω , Pt50 Ω ,
Ni508.4 Ω
4 to 20 mA, 0 to
20 mA, 0 to 10 V,
± 10 V, 0 to 5 V,
± 5 V, 1 to 5 V,
0 to 1.25 V, ± 1.25 V
R, S, K, J, T, L, B
Pt100(JIS, IEC),
JPt100
4 to 20 mA, 0 to
10 V,
0 to 5 V, 1 to 5 V
B, E, J, K, N, R, S, T
Variable range:
± 80 mV DC
Pt100
(JIS, IEC), JPt100
Ni508.4 Ω
I/O type
Standard accuracy: ± 0.05% of F.S.
Temperature coefficient: ± 0.01%/°C
Resolution: 1/64,000
Conversion period: 20 ms/4 pts,
Standard accuracy: ± 0.05% of F.S.
or ± 0.1 ° C, whichever is larger
Temperature coefficient: ± 0.009%/
° C
Resolution: 1/64,000
Conversion period: 20 ms/4 pts,
Standard accuracy: ± 0.05% of F.S.
Temperature coefficient: ± 0.008%/
° C
Resolution: 1/64,000
Conversion period: 20 ms/4 pts,
Centigrade Selected
Total accuracy: ± 0.3% of PV or ± 1°C
whichever is larger, ± 1 digit max.
Conversion period: 250 ms/Unit
Centigrade Selected
Total accuracy:
± 0.3% of PV or ± 0.8°C,
whichever larger, ± 1 digit max.
Conversion period: 250 ms/Unit
Standard accuracy: ± 0.3% of F.S.
Resolution: 1/16,000
Conversion period:
250 ms/8 inputs
Standard accuracy: ± 0.1%
Temp. coefficient: ± 0.015%/ ° C
Resolution: 1/4,096
Conversion cycle: 150 ms/4 pts
Standard accuracy: ± 0.1% or
± 0.1 ° C, whichever is larger
Temperature coefficient: ± 0.015%/
° C
Resolution: 1/4,096
Conversion period: 100 ms/4 pts
Standard accuracy: ± 0.2% or ± 0.2 ° C,
whichever is larger
Temperature coefficient: ± 0.015%/ ° C
Resolution: 1/4,096
Conversion period: 100 ms/4 pts
Features
• Dramatic reductions in installation cost, space, and set-up steps are
• Process value alarms and rate-of-change calculations can be exe-
• Rate-of-change limits and high/low output limits calculated for analog
• Peak/bottom hold and top/valley hold functions can be used for pro-
• Zero point and span can be adjusted for any specified range, and
• Changes exceeding a set threshold can be counted, and analog
• Reduced wiring with MIL connectors (CS1W-AD161 only).
attained by eliminating the need for external setters and converters.
cuted from temperature and analog inputs.
output.
cess values (CS1W-P@@1@ only).
adjustment days and times can be automatically saved. The adjust-
ment deadline and adjustment deadline expiration notice can also be
set and notification given (CS1W-P@@1@ only).
input values can be integrated (CS1W-P@@1@ only).
XW2D-34G6 Connector-Terminal Block Conversion Unit can be
used.
Main specifications
(See note.)
10 ms/2 pts
10 ms/2 pts
10 ms/2 pts
Output scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection alarm
Top/bottom/valley hold
Zero/span adjustment for any specified range
Output scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection alarm
Top/bottom/valley hold
Zero/span adjustment for any specified range
Output scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection alarm
Top/bottom/valley hold
Zero/span adjustment for any specified range
Process value alarms (H, L)
Input disconnection detection
Process value alarms (H, L)
Input disconnection detection
Process value alarms (H, L)
Input disconnection alarm
Variable range setting
Scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection detection
Variable range setting
Output scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection alarm
Variable range setting
Output scaling ( ± 32,000)
Process value alarms (HH, H, L, LL)
Rate-of-change calculation and alarm
Input disconnection detection
Main functions
Overview
23