CS1W-BAT01 Omron, CS1W-BAT01 Datasheet - Page 25

no-image

CS1W-BAT01

Manufacturer Part Number
CS1W-BAT01
Description
"BATTERY,CPU,CS1 SERIES ONLY"
Manufacturer
Omron
Datasheets

Specifications of CS1W-BAT01

Rohs Compliant
YES
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Process and Analog I/O Units
Overview of Analog I/O Units
Note: 1. The resolution and conversion speed can be switched with a DM setting.
Analog Input Unit
Analog Output Unit CS1W-DA041
Analog I/O Unit
2. Use the OMRON XW2D-34G6 Connector-Terminal Block Conversion Unit and XW2Z-200C Connecting Cable to wire inputs.
Name
If it isn’t necessary to change the setting, the Unit can be used with the earlier model’s mode (resolution of 1/4,000 and conversion speed
of 1 ms) just like the conventional model.
CS1W-AD041-V1
CS1W-AD081-V1
CS1W-AD161
(See note 2.)
CS1W-DA08V
CS1W-DA08C
CS1W-MAD44
Model
4 inputs
8 inputs
16 inputs
4 outputs
8 outputs
8 outputs
4 inputs
4 outputs
Number
of I/O
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V,
4 to 20 mA
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V,
4 to 20 mA
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V,
4 to 20 mA
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V,
4 to 20 mA
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V
4 to 20 mA
Input:
1 to 5 V, 0 to 5 V,
0 to 10 V, –10 to 10 V,
4 to 20 mA
Output:
1 to 5 V, 0 to 5 V, 0 to
10 V, –10 to 10 V
I/O signal ranges
Voltage input: ±0.2% of F.S.: current input ±0.4% of F.S.
(23±2°C)
Voltage input: ±0.4% of F.S.: current input ±0.6% of F.S.
(0 to 55°C)
Resolution: 1/8,000 (See note 1.)
Conversion speed: 250 µs/point max. (See note 1.)
(Can be used with a resolution of 1/4,000 and conversion speed
of 1 ms.)
Voltage input: ±0.2% of F.S.: current input ±0.4% of F.S.
(23±2°C)
Voltage input: ±0.4% of F.S.: current input ±0.6% of F.S.
(0 to 55°C)
Resolution: 1/8,000 (See note 1.)
Conversion speed: 250 µs/point max. (See note 1.)
(Can be used with a resolution of 1/4,000 and conversion speed
of 1 ms.)
Voltage input: ±0.2% of F.S.: current input ±0.2% of F.S.
(23±2°C)
Voltage input: ±0.4% of F.S.: current input ±0.4% of F.S.
(0 to 55°C)
Resolution: 1/8,000 (See note 1.)
Conversion speed: 250 µs/point max. (See note 1.)
(Can be used with a resolution of 1/4,000 and conversion speed
of 1 ms.)
Voltage output: ±0.3% of F.S.: current output ±0.5% of F.S.
(23±2°C)
Voltage output: ±0.5% of F.S.: current output ±0.8% of F.S.
(0 to 55°C)
Resolution: 1/4,000
Conversion speed: 1 ms/point max.
±0.3% of F.S. (23±2°C)
±0.5% of F.S. (0 to 55°C)
Resolution: 1/4,000
Conversion speed: 1 ms/point max.
±0.5% of F.S. (23±2°C)
±0.8% of F.S. (0 to 55°C)
Resolution: 1/4,000
Conversion speed: 1 ms/point max.
Voltage input: ±0.2% of F.S.: current input ±0.4% of F.S.
(23±2°C)
Voltage input: ±0.4% of F.S.: current input ±0.6% of F.S.
Output: ±0.3% of F.S. (23±2°C)
Output: ±0.5% of F.S. (0 to 55°C)
I/O resolution: 1/4,000
Conversion speed: 1 ms/point max.
(0 to 55°C)
Overall accuracy
Overview of Analog I/O Units
25

Related parts for CS1W-BAT01