ZEN-10C2AR-A-V2 Omron, ZEN-10C2AR-A-V2 Datasheet - Page 66

100/240 VAC 6 IN, 4 OUT

ZEN-10C2AR-A-V2

Manufacturer Part Number
ZEN-10C2AR-A-V2
Description
100/240 VAC 6 IN, 4 OUT
Manufacturer
Omron
Series
ZEN V2r
Type
Expandabler

Specifications of ZEN-10C2AR-A-V2

Voltage - Supply
100 ~ 240VAC
Number Of I /o
6 Input, 4 Output
Display Type
LED
Output Type
Relay
Voltage Rating
100 V to 240 V
Input Type
AC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Kit Contents
-
Analog Inputs
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
Z2680
ZEN10C2ARAV2
Wiring
Connecting 2-Wire AC Sensors
Two-wire
sensor
Note
A two-wire sensor cannot be connected directly to the AC input. To
connect a two-wire sensor, attach an external bleeder resistance in
the way shown below.
• Example: Connecting to a CPU Unit or Expansion I/O Unit
Calculating the Bleeder Resistance
when Connecting an OMRON E2E-
X10Y 2-Wire AC Sensor
This calculations in this example
are based on an input voltage of
85 to 110 V AC.
The following values are from the
Sensor datasheet.
The Sensor's maximum leakage
current is 1.7 mA.
The minimum current when the
Sensor's OFF residual voltage is
a)
b)
Use a resistance that satisfies both of the following
conditions.
Because of heat generation, use a resistor with at least the
following wattage.
R1 ( Ω ) ≤
R2 ( Ω ) ≤
P (W) ≥
R
I0 to I5
( Voltage supplied
to sensor)
Resistance value
Voltage supplied to sensor (V)
Min. current for which the
sensor’s OFF residual voltage is
less than 25 V (A)
Max. OFF-voltage for AC input (25 VAC)
Sensor’s max. leakage current (A)
N
L
2
× 3 (allowance factor)
E2E-X@Y@
Load residual
voltage
Internal
circuit
Output residual voltage
Section 2-2
Load current (mA)
At 100 V AC
100 VAC
OFF
ON
43