750-841 WAGO, 750-841 Datasheet - Page 166
750-841
Manufacturer Part Number
750-841
Description
CONTR.ETHERNET TCP/IP 10/100MBIT
Manufacturer
WAGO
Datasheet
1.750-841.pdf
(288 pages)
Specifications of 750-841
Rohs Compliant
YES
No. Of Digital Inputs
10
No. Of Digital Outputs
10
- Current page: 166 of 288
- Download datasheet (4Mb)
158 •
4.2.3.6 Function Code FC6 (Write single register)
Fieldbus Communication
MODBUS Functions
This function writes the value of one single output register to a slave device in
word format.
Request
The request specifies the reference number (register address) of the first
output word to be written. The value to be written is specified in the “Register
Value” field. The reference number of the request is zero based; therefore, the
first register starts at address 0.
Example: Write a value of 0x1234 to the second output register.
Response
The reply is an echo of the inquiry.
Exception
Byte
Byte 0, 1
Byte 2, 3
Byte 4, 5
Byte 6
Byte 7
Byte 8, 9
Byte 10, 11
Byte
.....
Byte 7
Byte 8, 9
Byte 10, 11
Byte
.....
Byte 7
Byte 8
Field name
Transaction identifier
protocol identifier
length field
Unit identifier
MODBUS function code
reference number
Register Value
Field name
MODBUS function code
Reference number
Register Value
Field name
MODBUS function code
Exception code
Example
0x0000
0x0000
0x0006
0x01 not used
0x06
0x0001
0x1234
Example
0x06
0x0001
0x1234
Example
0x85
0x01 or 0x02
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Related parts for 750-841
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
4 CHAN DIG INPUT 5VDC .2mS
Manufacturer:
WAGO
Datasheet: