54
E5EZ-PRR
Meaning
Action
Operation at Error
Meaning
Action
Operation at Error
Meaning
Action
Operation at Error
Platinum resistance thermometer input (Except for models with
a setting range of 199.9 to 500.0 C)
Thermocouple input (Except for models with a setting range of
ES1B
199.9 to 400.0 C)
s.err display
Analog (current, voltage) Input
s.err display
----
When display range < control range
e111
err
Input indication range
[[[[ display
Control range
Numeric display
( 199.9)
1999
Potentiometer Input Error
Motor Calibration Error
Memory Error
s.err display
Input indication range
Numeric display
Control range
Display range
(999.9)
9999
Internal memory operation is in error.
First, turn the power OFF then back ON again. If the display remains the same,
the Controller must be repaired. If the display is restored, then the probable
cause is electrical noise affecting the control system. Check for electrical noise.
Control output and alarm output turn OFF.
Valve opening has exceeded its regular range of 10% to 110%.
Check to see if there have been any wiring errors, burnouts, or short-circuits in
the potentiometer.
If there are no problems with the wiring, you can restart the power supply. If the
display remains the same, the Controller must be replaced. If the display is re-
stored, then the probable cause is interference which should be avoided.
Control output will output MV based on the “MV during error” setting position.
Alarm output will operate as normal.
Motor calibration did not completely finish.
After confirming the potentiometer and the wiring of the motor driving valve, per-
form motor calibration again.
Control output and alarm output set to OFF.
]]]] display
Platinum resistance thermometer input (Except for models with
a setting range of 199.9. to 500.0 C)
Thermocouple input (Except for models with a setting range of
s.err display
199.9 to 400.0 C)
s.err display
[[[[ display
Analog Input
s.err display
When display range > control range
( 199.9)
Control range
1999
Input indication range
Numeric display
Input indication range
Numeric display
Control range
Display range
s.err display
s.err display
(999.9)
9999