2726188 Phoenix Contact, 2726188 Datasheet - Page 109

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
Mounting side by side
(Inline Modular IO)
End clamps
(Inline Modular IO)
End plate
(Inline Modular IO)
Order of the Inline
terminals
6452_en_02
9.6
9.6.1
An Inline station is set up by mounting the individual components side by side. No tools are
required. Mounting the components side by side automatically establishes the potential and
bus signal connections between the individual station components.
After a station has been set up, individual terminals can be exchanged by pulling them out
or plugging them in. Tools are not required.
Mount end clamps on both sides of the Inline station. The end clamps ensure that the Inline
station is correctly mounted. End clamps secure the Inline station on both sides and keep it
from moving from side to side on the DIN rail. For the recommended end clamps, please
refer to "Ordering data" on page 11-7.
When mounting on a horizontal DIN rail, the end clamps can be snapped onto the DIN rail
at any point during station assembly.
When mounting on a vertical DIN rail, secure the end clamp on the left at the start of station
assembly, so as to prevent the station from slipping down.
The end plate terminates an Inline station. It has no electrical function. It protects the station
against ESD pulses and the user against dangerous contact voltages. The end plate is
supplied with the bus coupler and does not have to be ordered separately.
When mounting, observe the correct order of the Inline terminals (see "Order of the
Inline Modular IO terminals" on page 9-22).
Mounting/removal
Inline Modular IO: Mounting/removal
Mounting/removing devices
PHOENIX CONTACT
9-13