2726188 Phoenix Contact, 2726188 Datasheet - Page 79

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
Table 7-1
6452_en_02
No.
Potential jumpers
1
2
3
4
5
6
7
(9)
Data jumper
8
Function
7.5 V DC
24 V DC
GNDL
24 V DC
24 V DC
GND
FE
FE spring
Potential and data jumpers (24 V DC area)
U
U
U
U
U
GND
FE
L+
ANA
L-
S
M
Meaning
See Figure 7-2 "Basic arrangement of potential and data jumpers" on page 7-8
Communications power for the bus interface
I/O supply for analog terminals
Ground of communications power and I/O supply for analog terminals
Segment circuit supply
(if necessary with overload protection)
Main circuit supply
(if necessary with overload protection)
Ground of segment and main supply
Functional earth ground
FE contact to the DIN rail
(for bus couplers, segment terminals, and power terminals for the SELV area)
Local bus
Terminal inputs and outputs are supplied with voltage via the segment circuit.
The voltage for the segment circuit can be tapped from the main circuit. In addition, some
terminals tap the voltage directly from the main circuit.
For more detailed information about the circuits that are created via the potential jumpers
U
Depending on the terminal function, not all of the jumpers listed in Figure 7-2 are present
on a terminal. Please refer to the circuit diagram of the terminal to see which jumpers are
available for a terminal and how they are internally connected. The circuit diagram is
shown in the terminal-specific data sheet.
L
, U
ANA
, U
M
, and U
S
, please refer to page 7-1.
Electrical potential and data routing (Inline Modular IO)
PHOENIX CONTACT
7-9

Related parts for 2726188