Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
Mounting
Removal
6452_en_02
9.6.2
Figure 9-16
Figure 9-18
Before removing the base, disconnect all the necessary connectors, so as to provide
access to the base latch.
When using extended double signal connectors (long connectors), please ensure that
you do not bend them back too far, as you may break the front snap-on mechanism.
Place the base onto the DIN rail from above (Figure 9-16, A) and press down firmly (B).
Plug the connectors into the base (Figure 9-17).
First, insert the front connector shaft latching (A).
Then press the top of the connector towards the base until it snaps into place (B).
Disconnect the power to the module.
If there is a labeling field, which covers several connectors, it may have to be removed.
Lift the connector that is to be removed by pressing on the back connector shaft
latching (Figure 9-18, A).
Remove the connector (B).
Insert a tool in the base latch and pull gently upwards (Figure 9-19, A). Pull the module
out from the DIN rail (B, C).
Inline Block IO: Mounting/removal
Snapping on the base
Removing a connector
Figure 9-17
Figure 9-19
Mounting/removing devices
Snapping on a connector
Removing the base