Datasheet
10 Connecting cables
6452_en_02
10.1
Excluding a few exceptions, the cables for the I/O and supply voltages are connected via
Inline connectors using the spring-cage method. This means that signals up to
250 V AC/DC and 8 A can be connected with a conductor cross-section of 0.08 mm
1.5 mm
Both shielded and unshielded cables are used with Inline Modular IO terminals or
Inline Block IO modules.
10.1.1
Figure 10-1
Wire the connectors according to your application.
When wiring, proceed as follows:
Please observe the permissible lengths for sensor/actuator cables (see "Cable
connection method/cross-section" on page 11-5 or terminal-specific data sheet).
For the connector pin assignment, please refer to the corresponding terminal-specific
data sheet.
Inline wiring is normally done without ferrules. However, it is possible to use ferrules. If
using ferrules, make sure they are properly crimped.
Strip 8 mm off the cable.
Push a screwdriver into the slot of the appropriate terminal point (Figure 10-1, detail 1),
so that you can insert the wire into the spring opening.
Phoenix Contact recommends using a SZF 1 - 0,6X3,5 screwdriver
(Order No. 1204517; see Phoenix Contact "CLIPLINE" catalog).
Insert the wire (Figure 10-1, detail 2). Remove the screwdriver from the opening. This
clamps the wire.
2
2
.
Connecting cables using Inline connectors
Connecting unshielded cables
Connecting unshielded cables
1
6452C032
PHOENIX CONTACT
Connecting cables
2
to
10-1