ZUP36-12/U TDK Corporation, ZUP36-12/U Datasheet - Page 24

PWR SUP BENCH PROG 0-36V 432W

ZUP36-12/U

Manufacturer Part Number
ZUP36-12/U
Description
PWR SUP BENCH PROG 0-36V 432W
Manufacturer
TDK Corporation
Series
ZUPr
Type
Enclosedr
Datasheets

Specifications of ZUP36-12/U

Number Of Outputs
1
Efficiency
84%
Voltage - Output
0 ~ 36V
Power (watts)
432W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 36 VDC @ 12A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
432W
Operating Temperature
0°C ~ 50°C
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Output Current (max)
12A
Input Voltage
85 to 265V
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Accuracy
0.02% + 20 mV
Brand/series
ZUP
Current, Output
12 A
Display Type
Digital Meter
Power, Output
432 W
Power, Rating
432 W (Max.)
Regulation, Line
0.01% + 2 mA⁄1 mV + 0.005%
Regulation, Load
0.01% + 5 mA⁄2 mV + 0.005%
Standards
UL Listed, CE Marked
Temperature Coefficient
30 ppm⁄°C (CV)⁄100 ppm⁄°C (CC)
Temperature, Operating, Maximum
50 °C
Temperature, Operating, Minimum
0 °C
Voltage, Input
85-265 VAC
Voltage, Noise
50 mV @ 20 MHz BW
Voltage, Output
36 VDC
Voltage, Ripple
5 mV @ 5 Hz to 1 MHz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1676
ZUP3612/U
3.8.4 External Control Connector -
3.9 REPACKAGING FOR SHIPMENT
The external control connector is configured for Local sensing and no external On/Off control. Refer to
Fig: 3-6 below for the default configuration description. The default configuration is: Local sensing,
Rear panel On/Off disabled (On/Off can be controlled by the Front panel or by the serial communication
port), and output voltage and current are controlled by the Front panel or by the serial communication
port. For other configurations, remove the contact that should be modified, and replace it with a new
one with a suitable connection. Replacement contacts are supplied in the packaging of the power
supply.
To ensure safe transportation of the instrument, it is recommended to use the original package. The
original packaging material is reusable. If the original package is not available, contact the Nemic-
Lambda Sales or service facility near you for details on obtaining suitable packaging and shipping
information. Please attach a tag to the power supply describing the problem and specifying the owner,
model number and serial number of the power supply.
VCVP
VCCP
RCCP
COM
- S
+S
14
P
2
13
1
On/Off
Output Good
VRFV
VRFI
RCVP
- LS
+LS
Fig. 3-6:
External Control connector - default configuration
(ZUP rear panel view)
Default configuration connections