ZUP10-40/U TDK Corporation, ZUP10-40/U Datasheet - Page 55

PWR SUP BENCH PROG 0-10V 400W

ZUP10-40/U

Manufacturer Part Number
ZUP10-40/U
Description
PWR SUP BENCH PROG 0-10V 400W
Manufacturer
TDK Corporation
Series
ZUPr
Type
Programmabler
Datasheets

Specifications of ZUP10-40/U

Load Regulation
0.01%
Voltage - Output
0 ~ 10V
Number Of Outputs
1
Power (watts)
400W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 10 VDC @ 40A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
400W
Operating Temperature
0°C ~ 50°C
Efficiency
82%
Approvals
CE, EN, UL
Line Regulation
0.01%
Power Supply Output Type
Variable
No. Of Outputs
1
Output Voltage
10V
Output Current
40A
Power Rating
400W
Input Voltage
85V AC To 265V AC
Length
350mm
Width
70mm
Accuracy
0.02% + 8 mV
Brand/series
ZUP
Current, Output
40 A
Display Type
Digital Meter
Power, Output
400 W
Power, Rating
400 W (Max.)
Regulation, Line
0.01% + 2 mA⁄1 mV + 0.005%
Regulation, Load
0.01% + 5 mA⁄2 mV + 0.005%
Standards
UL Listed, CE Marked
Temperature Coefficient
30 ppm⁄°C (CV)⁄100 ppm⁄°C (CC)
Temperature, Operating, Maximum
50 °C
Temperature, Operating, Minimum
0 °C
Voltage, Input
85-265 VAC
Voltage, Noise
50 mV @ 20 MHz BW
Voltage, Output
10 VDC
Voltage, Ripple
5 mV @ 5 Hz to 1 MHz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1669
ZUP1040/U
5.7 SERVICE REQUEST
5.7.1 Service Request (SRQ)
Service request is a message generated by the ZUP power supply to interrupt the controller. SRQ
can be generated by a power supply fault condition.
Each of the following conditions can generate SRQ message:
1. Over Voltage Protection (OVP).
2. Over Temperature Protection (OTP).
3. Foldback Protection.
The operator decides which of the conditions are defined as faults. Enabling or disabling a condition
from generating SRQ message does not affect the condition within the power supply.
5.7.2 Service Request message
The service request message consists of three characters terminated by EOS<CR><LF>.
The first character identifies the SRQ cause: 1-Foldback , 2-OVP , 3-OTP.
The 2’nd and 3’rd characters identify the ZUP power supply address.
Example: String generated by a ZUP unit :120<CR><LF> , means foldback protection was activated
5.7.3. Service request enable/disable commands
1
2
3
4
5
6
#
:SRVn;
:SRV?;
:SRTn;
:SRT?;
:SRFn;
:SRF?;
Command
in power supply address 20.
Description
Returns QT followed by the OTP service request status.
Enable or disable Foldback protection service request.
Returns QF followed by the Foldback protection service request status
Enable or disable OVP service request.
Returns QV followed by the OVP service request status.
:SRV1; Enable OVP service request.
:SRV0; Disable OVP service request.
:QV1; OVP service request enabled.
:QV0; OVP service request disabled.
Enable or disable OTP service request.
:SRT1; Enable OTP service request.
:SRT0; Disable OTP service request.
:QT1; OTP service request enabled.
:QT0; OTP service request disabled.
:SRF1; Enable Foldback protection service request.
:SRF0; Disable Foldback protection service request.
:QF1; Foldback protection service request enabled.
:QF0; Foldback protection service request disabled.