Specifications of Y92S-38

Accessory Type
Tool - Lock Key Pen
For Use With/related Products
H3DS Series
For Use With
H3DS-SLCAC24-230/DC24 - TIMER CAGE CLAMP 17.5MM 4MODESH3DS-MLCAC24-230/DC24-48 - TIMER CAGE CLAMP 17.5MM 8MODESZ2395 - RELAY TIME DELAY 4MODE DIN MNTZ2394 - RELAY TIME DELAY 1MODE DIN MNTZ2393 - RELAY TIME DELAY 8MODE DIN MNTZ2392 - RELAY TIME DELAY 1MODE DIN MNT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Color
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
Y92S38
Z2396
H3DS
I \
Note: For reference:
Accuracy of operating time ± 1% max. of FS ( ± 1% ± 10 ms max. at 1.2-s range)
Setting error
Signal input time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Impulse withstand voltage
Noise immunity
Static immunity
Life expectancy
EMC
Case color
Degree of protection
Weight
Characteristics
A maximum current of 0.15 A can be switched at 125 VDC (cos φ =1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
± 10% ± 50 ms max. of FS
50 ms min.
± 0.7% max. of FS ( ± 0.7% ± 10 ms max. at 1.2-s range)
± 2% max. of FS ( ± 2% ± 10 ms max. at 1.2-s range)
100 M Ω min. at 500 VDC
Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.
Between control output terminals and operating circuit: 2,000 VAC for 1 min.
Between contacts not located next to each other: 1,000 VAC for 1 min.
Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Malfunction: 100 m/s
Destruction: 1,000 m/s
3 kV (between power terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µ s, 1-ns rise) ± 1.5 kV
Malfunction: 4 kV
Destruction: 8 kV
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) See Note.
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
Light gray (5Y7/1)
IP30 (Terminal block: IP20)
Approx. 70 g
2
3 times each in 6 directions
2
EN55011 Group 1 class B
EN55011 Group 1 class B
3 times each in 6 directions
8 kV air discharge (level 3)
1 kV control port with capacitive clamp (level 3)
1 kV differential mode (level 3)
H3DS