Checking the Program
Error Messages
120
A
B
C
Rank
????
Block err
Dup # error
JME missing
Loc. error
No END instr
Operand err
SBN missing
Step error
Undef. Step #
IL-ILC error
SBN-RET error
Dup output err
JMP missing
SBS missing
SFC error
Message
The errors will be displayed when the program check is complete. If the errors
cannot be displayed on a single page, use the PgDn and PgUp Keys to switch
between the pages. If no errors were found, a message will be displayed to in-
form you.If error messages are displayed, correct the program and run the pro-
gram check again. Press the Esc Key or Shift+Esc Keys to return to the main
menu.
The time required for the program check depends on the size of the program. It
may take over 2 minutes.
Program contents destroyed. Invalid
instruction code.
Syntax error in instruction block. Number
of LD instructions disagrees with number
of logic block instructions (OR LD, AND
LD).
SBN or JME number used twice.
No JME corresponding to JMP.
Instruction used in incorrect memory
area
No END instruction in the program
Incorrect operand set for an instruction.
No SBN corresponding to SBS.
STEP, SNXT used incorrectly.
Step number used incorrectly.
IL, ILC not used in pairs.
RET instruction or SBN-RET used
incorrectly.
Same output bit specified for more than
one instruction controlling its status.
No JMP address corresponding to JME
address.
No SNS address corresponding to SBN
address.
Incorrect SFC program.
Description
Enter correct instructions at the ????
parts of the program.
Check the program.
Check and correct program
Check use of instruction and correct
program
Enter an END instruction at the end of
the program.
Enter correct operand.
Check and correct program
Check and correct program
Correct the bit addresses. This problem
can cause racing.
Check and correct program
Remedy
Section 3-11