Editing Network Support Tables
Error Message Table
Clearing Data Link Tables
Saving Data Link Tables
Retrieving Data Link Tables
172
DM Begin Wd err
DM exceeded
Dup node address
I/O Begin Wd err
I/O exceeded
Link node range err
Node range err
Too many DM link
Wd
Too many I/O link
Wd
Too many words
Error message
The DM start word address lies out of range.
The DM link area lies out of range.
Duplicate node addresses set.
The I/O start word address exceeds CIO 2555.
The data link area exceeds CIO 2555.
The number of link nodes lies outside the range
2 to 32.
A node address is set outside the range 1 to
126.
Number of DM words lies outside the range 1
to 127.
Number of I/O words lies outside the range 1 to
127.
The total number of I/O and DM words for all
nodes exceeds 3,584.
1, 2, 3...
1, 2, 3...
1, 2, 3...
Note Enter the file name as up to 8 characters. Lower-case characters are converted
Be sure the data disk has been formatted and is not write-protected. Data link
table data cannot be saved if it exceeds the free space available on the data disk.
to upper-case. A single directory name can have up to 8 characters with a total of
66 characters for the entire path name. See 6-2 File Management for more infor-
mation about directories.
or
1. Select “C:Clear data link table” from the SYSMAC NET menu.
2. Press the Y and Enter Keys to clear the contents of the data link table.
1. Select “S:Save data link table” from the SYSMAC NET menu. A file name
2. Enter the file name and press the Enter Key.
3. If the input file name already exists, a message will ask if the file should be
4. Input the title and press the Enter Key.
1. Select “L:Retrieve data link table” from the SYSMAC NET menu.
Error description
Press the Enter Key to cancel and return to the menu.
input area will be displayed.
To enter an existing file name, press the End Key or Ctrl+M Keys to display
the current file names, select the required file name with the cursor, and
press the Enter Key.
overwritten. Press the Y and Enter Keys to overwrite the file. Press the Enter
Key to cancel and input a new file name.
The title input area will appear when the Enter Key is pressed.
The title can be up to 30 characters long.
A message will flash while the table is being saved. The data link table will be
displayed after the data is saved.
Set the DM start word address within the
prescribed range.
Set the DM link area so that the limit is not
exceeded by reducing the number of DM words
or lowering the DM first word.
Do not set the same node address twice.
Set the I/O start word address to CIO 2555 or
below.
Set the I/O link area to CIO 2555 or below by
reducing the number of I/O words or lowering
the I/O first word.
Change settings to bring the number of link
nodes inside the range 2 to 32.
Set the node address within the range 1 to 126.
Change the settings to bring the number of DM
words within the range 1 to 127.
Change the settings to bring the number of I/O
words within the range 1 to 127.
Reduce the total number of I/O and DM words
to below 3,584.
Remedy
Section 4-6