Specifications of MCR-C-UI-UI-DCI-NC
Input Type
Configurable
Output Type
Configurable
No. Of Output Channels
1
Accuracy
± 0.1%
Supply Voltage Range
18VDC To 30VDC
Approval Bodies
CE, GL, UL Recognised
External Depth
114.5mm
External Length /
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Signal Conditioner Input
0V To 10V
Signal Conditioner Output
0V To 10V
100238_en_02
Specifying the Input Signal Range via DIP Switch 1
Specifying the Output Signal Range via DIP Switch 2
Select one of the possible signal ranges using the appropri-
ate configuration of DIP switch 1 according to the table.
Exception: Bipolar input signals are not permitted for the
4 … 20 mA and 1 … 5 V output signal ranges.
Output With Simple Adjustment (0 ... 5 V/0 ...10 V)
Set the output range via DIP switch 2. Please note the selec-
ted input range. Specify the initial and final value of the input
signal using a calibration device. Adjust the output value with
a digital multimeter.
Adjustment after specifying the initial and final value for the
0 ... 5 V output: Set 0 V ±0.5 mV at the "ZERO" potentiome-
ter and 5 V ±0.5 mV at the "SPAN" potentiometer.
Adjustment after specifying the initial and final value for the
0 ... 10 V output: Set 0 V ±0.5 mV at the "ZERO" potentiome-
ter and 10 V ±0.5 mV at the "SPAN" potentiometer.
MCR-C-UI-UI(-450)-DCI(-NC)
PHOENIX CONTACT