MCR-C-UI-UI-DCI-NC

Manufacturer Part Number
MCR-C-UI-UI-DCI-NC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-C-UI-UI-DCI-NC

Input Type
Configurable
Output Type
Configurable
No. Of Output Channels
1
Accuracy
± 0.1%
Supply Voltage Range
18VDC To 30VDC
Approval Bodies
CE, GL, UL Recognised
External Depth
114.5mm
External Length /
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Signal Conditioner Input
0V To 10V
Signal Conditioner Output
0V To 10V
100238_en_02
Output With Adjustment Point Calculation (±5 V/±10 V/
1 ... 5 V/0 ... 5 mA/0 ... 10 mA/0 ... 20 mA/4 ... 20 mA)
Set the output range via DIP switch 2. Please note the selec-
ted input range.
Specify the initial and final value of the input signal using a
calibration device.
Record the output value measured with a digital multimeter.
For adjustment with the calibration device, specify the final
value of the input signal range as follows:
"SPAN" potentiometer: Full-scale adjustment point A ± ad-
justment tolerance
"ZERO" potentiometer: Output final value ± adjustment tole-
rance
Calculation of full-scale adjustment point A: A = Measured
value 1 x Constant/Measured value 2 - Measured value 1
±5 V, ±10 V, 1 ... 5 V, 4 ... 20 mA output signal ranges: If the
initial value is specified at the input, measured value 1 is out-
put at the output. If the final value is specified at the input,
measured value 2 is output at the output.
0 ... 20 mA output signal range: If the initial value +10% of the
range is specified at the input, measured value 1 is output at
the output. If the final value is specified at the input, measu-
red value 2 is output at the output.
For the values for the constant, output final va-
lue, and adjustment tolerance, please refer to
the corresponding tables.
MCR-C-UI-UI(-450)-DCI(-NC)
PHOENIX CONTACT
11