CRT1-ID16TAH Omron, CRT1-ID16TAH Datasheet - Page 141

no-image

CRT1-ID16TAH

Manufacturer Part Number
CRT1-ID16TAH
Description
16 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID16TAH

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
4-1-2
4-1-3
Basic Specifications of Slave Units
Communications power supply voltage 14 to 26.4 VDC
I/O power supply voltage
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Insulation resistance
Ambient operating temperature
Ambient operating humidity
Ambient operating atmosphere
Storage temperature
Storage humidity
Terminal block screw tightening torque
(See note.)
Installation
MS
Name
Lit green.
Lit red.
Flashing red.
Not lit.
Indicator status
Performance Specifications
Communications Indicators
Item
Note
Normal status
Fatal error
Non-fatal error
Power OFF/Startup
Node/communications
Applicable only to Slaves to which screw terminal blocks are mounted.
Some of the specifications are different for the CRT1-ROS08/ROS16 (with
relay outputs) and the CRT1-ROF08/ROF16 (with SSR outputs). For details,
refer to 5-3-8 Sixteen-point Output Units (2-tier Terminal Block with Relay Out-
puts) and 5-3-9 Sixteen-point Output Units (2-tier Terminal Block with SSR
Outputs).
The communications indicators have the following meanings.
MS (Module Status): Indicates the status of the node with a two-color LED
(green/red).
NS (Network Status): Indicates the status of communications with a two-color
LED (green/red).
20.4 to 26.4 VDC (24 VDC −15%/+10%)
Conforms to IEC 61000-4-4, 2 kV (power line).
10 to 60 Hz with double-amplitude of 0.7 mm, 60 to 150 Hz and 50 m/s
and Z directions for 80 min each
150 m/s
500 VAC (between isolated circuits)
20 MΩ min. (between isolated circuits)
−10 to 55°C
25% to 85% (with no condensation)
No corrosive gases
−25 to 65°C
25% to 85% (with no condensation)
M3 wiring screws: 0.5 N⋅m
M3 mounting screws: 0.5 N⋅m
Mounting with 35-mm DIN Track, M4 screws, or Mounting Brackets (depending
on model)
status
2
(3 times each in 6 directions on 3 axes)
The Unit is operating normally.
A hardware error has occurred in the Unit. The watchdog
timer has timed-out.
There is an error in the switch settings.
An EEPROM checksum error has occurred.
The power supply is OFF, the Unit is being reset, or the Unit
is being initialized.
Specification
Meaning
Section 4-1
2
in X, Y,
117

Related parts for CRT1-ID16TAH