CRT1-ID16TAH Omron, CRT1-ID16TAH Datasheet - Page 355

no-image

CRT1-ID16TAH

Manufacturer Part Number
CRT1-ID16TAH
Description
16 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID16TAH

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Switch Settings
Setting the Node Address
Setting the Input Ranges
Units with Screw Terminal Blocks
Note
■ Input CH0/CH1 range (common)
The node address is set as a decimal number with the 10s digit set on the left
rotary switch and the 1s digit set on the right rotary switch. (The maximum
node address is 63.)
The setting on the rotary switches is read when power is turned ON.
Pin No.
1
2
3
4
5
6
7
8
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
1
(1) Always use the default setting (OFF) for pin 7.
(2) Always set pin 8 to ON if the DIP switch is used to set the ranges. If this
(3) The DIP switch settings are read when the power is turned ON.
0
2
pin is OFF, the DIP switch settings will not be enabled.
Input range
3
Input CH0/CH1 range settings
(common)
Input CH2/CH3 range settings
(common)
Always OFF.
Range setting method
4
0
5
6
1s digit of node address
10s digit of node address
Setting
7
8
OFF
ON
OFF
ON
OFF
ON
ON
Pin 1
Default setting: All pins OFF
See the next table
Default setting: All pins OFF
See the next table
Always set this pin to OFF. Malfunctions
may occur if it is set to ON.
OFF: Use CX-Integrator.
ON: Use DIP switch.
OFF
OFF
ON
ON
OFF
OFF
Pin 2
Specification
OFF
OFF
OFF
OFF
ON
ON
Section 6-6
Pin 3
331