CRT1-ID16TAH Omron, CRT1-ID16TAH Datasheet - Page 489

no-image

CRT1-ID16TAH

Manufacturer Part Number
CRT1-ID16TAH
Description
16 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID16TAH

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Component Names and Functions (Same for CRT1B-MD04JS and CRT1B-MD04JS-1)
Display Section
Communications
indicators
I/O indicators
Setting the Node
Address
Bit Slave Units with Compact Connectors
CompoNet communi-
cations connector
(internal hook)
Left side of Unit
Node Address
Setting Switch
Refer to 4-1-3 Communications Indicators.
The indicators show the status of the inputs.
Using the node address switch, set the node address to a 7-bit binary value
between 00000000 and 1111111 (0 to 127 decimal). Communications will not
be performed if the node address is set out of range. The factory setting is
0000000.
Refer to Appendix F Node Address Settings for Bit Slave Units with Compact
Connectors for the relation between decimal node addresses and switch set-
tings.
IN0, IN1,
OUT0, OUT1
Name
ON
RSV - Not used (keep OFF).
64
32
16
8
4
2
1
Communications
indicators (MS, NS)
Front of Unit
Lit yellow.
Not lit
LED status
I/O indicators
(IN0, IN1, OUT0, OUT1)
I/O connector
labels
Input ON
Input OFF
Status
OUT0
OUT1
I/O connectors
(IN0, IN1, OUT0, OUT1)
The input is ON.
The input is OFF.
Right side of Unit
Section 9-5
Meaning
465
IN0
IN1

Related parts for CRT1-ID16TAH