Specifications of H3DS-SL AC24-230/DC24-48

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC, 24 ~ 48VDC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage, Trigger Signal
Timing Range
0.1 s to 120 Hrs
Supply Voltage
24 V to 230 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3DSSLAC24230DC2448
Z2395
H3DS-F
I
I
Selector Settings
The selectors can be turned clockwise and counterclockwise to
select the desired time scale or operating mode.
Each selector has a snap mechanism that secures the selector at
a given position. Set the selector at a position at which it is
secured. Do not set it midway between two secure positions, or a
malfunction could result from improper setting.
Settings for ON-Start/OFF-Start
If voltage is applied to terminal B1, or if terminals A1 and B1 are
shorted, the operating mode is switched to ON-start mode. If
these terminals are disconnected, the mode switches to OFF-
start mode. The operating mode will not change if the state of the
applied voltage changes during timer operation.
Selection of Time Scale
The time scale is selected by turning the ON-time scale selector
and OFF-time scale selector. The time scales will appear in the
following order in each time scale display window on the left of
the selector:
0.1 s, 1 h, 0.1 h, 1 m, 1 s, 0.1 h, 0.1 m, 1 s.
Note:
Inputs
Outputs
ON-time scale
display window
and selector
I/O Function
Basic Operation
The time scales “1 s” and “0.1 h” appear twice. Both instances
indicate exactly the same time scale.
Control output
OFF-time scale display
window and selector
ON-start operation begins when inputs are turned ON.
Outputs are turned ON/OFF according to the time set by the ON-time and OFF-time setting dial.
Time Setting
Use the ON-/OFF-time setting dials to set the ON-/OFF time.
Locking/Unlocking Selectors and the Time Setting Dial
The ON-/OFF-time setting dials and time scale selectors can be
locked using the Y92S-38 Lock Key, a special pen type tool that is
sold separately. To lock the dials or selectors, insert the Lock Key
in the keyhole to the lower right of the dial or selector and turn it
clockwise until the dial or selector is completely covered with the
red cover. To unlock, turn the Lock Key in the opposite direction.
Key hole