3.2 RUNNING APPLICATIONS THAT USE INTERNAL VARIABLES ONLY
The Target PLC and your PC must be connected through Ethernet, RS232 or RS485. Use the following
procedure to run any sample application that uses only internal variables:
1. Open the ISaGRAF Project Management by double-clicking on the ISaGRAF Projects icon on your
2. On the BOTTLEF - Programs window select Debug menu → Link setup. On the PC-PLC link
3. Select Debug menu → Debug to open the Debugger window. If Debugger window displays
4. Download the bottlef application by selecting File menu → Download. Select “RABBIT: TIC code for
OEM Technology Solutions
Desktop or selecting Start menu → Programs → ISaGRAF 3.5 → Projects. On the Projects
Management window, double-click on the bottlef project.
parameters window enter the Target Slave Number (corresponds to the Modbus Slave number of
the Target PLC) and the Communication port (ETHERNET for Modbus TCP or COM for Modbus RTU
over RS232/RS485):
a) If ETHERNET is selected press Setup button and enter the IP address of the target (default is
b) If serial COM port is selected (COM1 – COM4) press Setup button and select either 19200,
“<application name> active” message, stop the current application that is running by pressing the
Stop button
is displayed.
Rabbit-based controllers” on the Download window and press Download button. A progress bar on
the Debugger window will show the progress of the downloading process. Once the downloading is
completed the application runs immediately and the SpotLight window is displayed. In the
SpotLight, double-click on the START button and press TRUE button. The bottle production will
start.
192.168.1.100). Press OK button. Press OK button to close the PC-PLC link parameters
window
9600, 4800, 2400, 1200 or 600 baud rate depending on the current configuration of your
EMBEDDED
PLC BL2500 User’s Manual
Caution:
Do not change the port number from 1100 otherwise the Ethernet communication
with the ISaGRAF Workbench will not work. This port is used exclusively by the
communication between ISaGRAF Workbench and the
Note:
The
parameters are fixed: no parity, 8 data bits, 1 stop bit and no flow control.
Note also that ISaGRAF supports serial ports COM1 to COM4. If you are using a
USB-to-serial converter cable check that the com port assigned is between COM1
and COM4. If not, change the serial port settings on your Windows Operating
System (see Section 7.2). Many USB-to-serial converters are assigned to COM5
port or higher after its installation.
PLC target.
on the toolbar or select File menu → Stop application. A “No application” message
EMBEDDED
PLC Kernel supports baud rates from 19200 to 600. The other
EMBEDDED
Running Sample Applications
PLC target.