101-1108 Rabbit Semiconductor, 101-1108 Datasheet - Page 45

KIT EMBEDDED PLC APPLICATION

101-1108

Manufacturer Part Number
101-1108
Description
KIT EMBEDDED PLC APPLICATION
Manufacturer
Rabbit Semiconductor
Series
Coyoter
Type
MPU Moduler
Datasheet

Specifications of 101-1108

Contents
BL2500, ISaGRAF V3.50, Embedded PLC software kernel, ISaGRAF Programming Cable and Documentation
Processor To Be Evaluated
Rabbit 3000
Interface Type
RS-232, Ethernet
For Use With/related Products
BL2500
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Other names
316-1120
PLC BL2500 User’s Manual
Hardware Reference
EMBEDDED
Figure 9: BL2500 Multidrop Network
The BL2500 comes with a 220 W termination resistor and two 681 W bias resistors installed and enabled.
The load these bias and termination resistors present to the RS-485 transceiver limits the number of
BL2500s in a multidrop network to one master and nine slaves, unless the bias and termination resistors
are removed. When using more than 10 BL2500s in a multidrop network, or when you need the full
common-mode immunity per the RS-485 specification, leave the 681 W bias resistors in place on the
master BL2500, and leave the 220 W termination resistors in place on the BL2500 at each end of the
network.
Figure 10: RS485 Termination and Bias Resistors
4.5.2 Ethernet Port
Figure 11 shows the pinout for the RJ-45 Ethernet port (J4). Note that some Ethernet connectors are
numbered in reverse to the order used here.
Figure 11: RJ-45 Ethernet Port Pinout
Three LEDs are placed next to the RJ-45 Ethernet jack, one to indicate an Ethernet link (LNK), one to
indicate Ethernet activity (ACT), and one to indicate when the RCM3200 is connected to a functioning
100Base-T network (SPD).
The RJ-45 connector is shielded to minimize EMI effects to/from the Ethernet signals.
OEM Technology Solutions
Page 39