E53-COV04 Omron, E53-COV04 Datasheet - Page 27

no-image

E53-COV04

Manufacturer Part Number
E53-COV04
Description
E5CJ TERMINAL COVER
Manufacturer
Omron
Datasheet

Specifications of E53-COV04

Accessory Type
Terminal Cover
For Use With/related Products
E5CJ
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E53COV04
or F)
(E5jJ-jB Only)
Example
Display (E5jJ-jH Only)
Value Setting (E5jJ-jH
Only)
Parameters on Display Level 1
24
Output Value Display
- Input Shift Value
Control Period Setting
Heater Current Value
Heater Burnout Alarm
Hysteresis Setting ( C
,
,
, and
The output value is displayed within a range of 0.0% to 100.0%.
It is possible to set the control period within a range of 1 to 99 s. The control peri-
od is the period required by the E5jJ to turn ON and OFF its relay output or volt-
age output. The ON period increases in proportion to the output value. If the con-
trol period is short, smooth control operation will be possible although a short
control period shortens the life of the relay if relay output is used. Therefore, the
control period should not be less than 20 s if relay output is used. The following
are output examples with an output value of 50.0 %.
It is possible to set the hysteresis for the E5jJ in ON/OFF control operation with-
in a range of 0.1 to 999.9 C/ F.
It is possible to set
(set point 3) all in Celsius or Fahrenheit regardless of the set point presently se-
lected. To select the set point, open or short-circuit terminals EV1 and EV2. Re-
fer to Section 7 Event Input Function for details.
It is possible to set the input shift value within a range of –199.9 to 999.9 C/ F.
When an input shift value is set, the process value will be the input value added
with the shift value.
After the input shift value is set, the it is effective even if the input shift value dis-
play is turned off on the engineering level.
It is possible to set the heater current value within a range of 0.0 to 55.0 A. If the
current value exceeds 55.0 A,
The heater current will be processed and displayed if the control output is ON.
It is possible to set the heater burnout alarm value within a range of 0.0 to 50.0 A,
which will be used to detect heater burnout. If the heater burnout alarm value is
set to 0.0 A, the heater burnout alarm output will be always OFF. If the heater
burnout alarm value is set to 50.0 A, the heater burnout alarm output will be al-
ways ON. Refer to Section 8 Heater Burnout Detection for details.
When the E5jJ is in advanced PID with fuzzy self-tuning mode, the following
parameters ( , , ,
following parameters). The fuzzy self-tuning always adjusts the PID constants to
the most suitable values according to the characteristics of the controlled de-
vice.
100 C
Input
0 (no compensation)
10.0 (compensation value)
–10.0 (compensation value)
Heating
control
(Reverse)
Cooling
control
(Normal)
Control period: 10 s
OFF
ON
- (set point 0),
5 s
Low temperature
Low temperature
) will not be displayed (i.e., there is no need to set the
OFF
ON
OFF
Input shift value
ON
will be displayed on the set value display.
Hysteresis
Set point
Set point
- (set point 1),
Hysteresis
OFF
ON
Control period: 20 s
10 s
High temperature
High temperature
- (set point 2), and
100 C
110 C
90 C
Process value
Section 3-5
-