E53-COV04 Omron, E53-COV04 Datasheet - Page 33

no-image

E53-COV04

Manufacturer Part Number
E53-COV04
Description
E5CJ TERMINAL COVER
Manufacturer
Omron
Datasheet

Specifications of E53-COV04

Accessory Type
Terminal Cover
For Use With/related Products
E5CJ
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E53COV04
Troubleshooting
4-2
The temperature does not reach the
set point.
Troubleshooting
Phenomenon
Note The stable range is set to 27 F with the E5jJ-jjjj-F.
HT may change the PID constants even though the PID constants are ideal for
the control system. Refer to 9-1 Engineering Level for details.
Fuzzy self-tuning may not exhibit its full capability due to the characteristics and
conditions of the controlled object.
Refer to the following table for troubleshooting when Unit operation is not
smooth.
The dead time measured was longer
than the actual value and
inappropriate PID constants were
obtained because the load (such as a
heater) was turned on after the
Temperature Controller started
operating. (Refer to 4-3-6 Startup for
details.)
The PID constants were changed from
the most ideal value because HT is
ON continuously when there was a
periodic temperature change larger
than the stable range due to an
external disturbance. Refer to the note
under 4-1-3.
Probable cause
External disturbance
Figure A: Waveform with HT turned ON
External disturbance
Figure B: Waveform with HT turned OFF
T1
T2
Do the following to execute SRT
again.
1) Set the control mode to the
2) Set the control mode to the
3) Wait until the temperature of the
Do either one of the following so that
HT will not be ON.
T1<T2
advanced PID and set the
proportional band to 0.1 C.
advanced PID with fuzzy
self-tuning again.
control system is stable, and then
turn on the Temperature Controller
and the load simultaneously or
turn on the load first for SRT.
Change the stable range to a
wider setting than the range of the
temperature change and execute
SRT again by executing steps 1)
to 3) above.
After obtaining the most ideal PID
constants by executing steps 1) to
3) above, set the control mode to
advanced PID.
Countermeasure
Section 4-2
31