E53-COV04 Omron, E53-COV04 Datasheet - Page 7

no-image

E53-COV04

Manufacturer Part Number
E53-COV04
Description
E5CJ TERMINAL COVER
Manufacturer
Omron
Datasheet

Specifications of E53-COV04

Accessory Type
Terminal Cover
For Use With/related Products
E5CJ
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E53COV04
Advanced PID
Models
1-1
Fuzzy Self-tuning
Auto-tuning
Event Input Function
Watertight Construction
Output Units
1-2
2
Factory-set to 2 (K)
Features
Models
INPUT
Temperature
range ( C)
Input
Selectable
internally.
Setting
no.
The basic features of the Thermac E5jJ Temperature Controller are outlined
below.
When using a conventional temperature controller for ideal temperature control,
it is necessary to adjust the PID constants of the temperature controller accord-
ing to the controlled device. The Thermac E5jJ Temperature Controller incor-
porates a fuzzy self-tuning function, thus allowing ideal temperature control
without any adjustment of the PID constants. The user needs only to set the
E5jJ to the desired temperature for ideal temperature control.
Auto-tuning is also available. It is useful when appropriate results are not
obtained through fuzzy self-tuning. (Refer to Section 10 Auto-tuning .)
It is possible to select a set point out of a maximum of two set values on the
E5CJ-jB and four set values on the E5AJ-jB via their event input terminals
from the PCs connected to these Temperature Controllers. The control opera-
tion of the E5AJ-jB via can be stopped with an event input signal.
The E5jJ can be used in places where water is sprayed onto the E5jJ, be-
cause the front panel of the E5jJ assures IP54 when the E5jJ is panel-
mounted (except for front panel of the E5CJ, which assures IP50). If greater wa-
tertightness is required, use the Y92A-jjN, a dedicated watertight cover (sold
separately).
The E5jJ incorporates an advanced PID function, which is also incorporated by
the Thermac X Temperature Controller. The advanced PID function prevents
temperature overshooting the moment the Temperature Controller starts oper-
ating, assures a short startup time, and performs ideal temperature control by
quickly responding to external disturbances.
The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for
driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output
Unit can be connected to any E5jJ Temperature Controller (except the E5CJ)
with ease according to the desired output configuration and application.
The thermocouples and platinum resistance thermometers listed in the follow-
ing table can be connected to any Thermac E5jJ Temperature Controller.
1300
1000
800
600
400
200
100
–100
–200
0
Platinum resistance
thermometer
–199.9
JPt100
650.0
0.8
Pt100
–199.9
650.0
1.9
–200
1300
2
K
–100
850
3
J
Thermocouple
400.0
–199.9
4
T
–100
850
5
L
–199.9
400.0
6
U
Section 1-2
–200
1300
7
N