NFK3-SC FLUKE NETWORKS, NFK3-SC Datasheet - Page 171

no-image

NFK3-SC

Manufacturer Part Number
NFK3-SC
Description
LAN Tester
Manufacturer
FLUKE NETWORKS
Datasheet

Specifications of NFK3-SC

Lead Free Status / RoHS Status
na
END 1-2
END 2-1
Output
Fiber
Input Fiber
RESULT
LIMIT
MARGIN
N/A
Item
These refer to the direction of the test results. If THIS END on the main tester is set to END 1, END 1-2
shows results for the main tester's output fiber; END 2-1 shows results for the input fiber. The results are
reversed if the main tester is set to END 2. Press
When bi-directional testing is enabled, Output Fiber and Input Fiber refer to the fiber connections at the
main tester after you swapped the fibers. The tester shows results for both test directions. Press
switch between the results for each fiber.
PASS: The measurement in the column is within the limit.
FAIL: The measurement in the column exceeds the limit.
The loss, length, or propagation delay result for the fiber. Propagation delay is half of the time taken for
the signal to travel from the tester's OUTPUT connector to the INPUT connector (minus the delay of the
reference test cords and adapters). "Too High" is shown if the loss is too high to measure.
If loss is negative, set the reference and test the cabling again. See Table 7-10 for details.
The maximum loss, length, or propagation delay allowed by the selected test limit.
The difference between the limit and the measured value. Margin is negative for measurements that fail.
The results show N/A for values not defined by the selected test limit.
Table 7-5. Smart Remote Mode RESULTS Screen Features
Description
A
to switch between the results for each fiber.
Testing in Smart Remote Mode
Using the Loss/Length Option
A
to
7-19
7