MCR-F-UI-DC Phoenix Contact, MCR-F-UI-DC Datasheet - Page 10

no-image

MCR-F-UI-DC

Manufacturer Part Number
MCR-F-UI-DC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-F-UI-DC

Input Type
0.1 Hz To 120 KHz
Output Type
Analogue Voltage Or Current
No. Of Output Channels
2
Accuracy
± 0.15%
Approval Bodies
UL Recognised
External Depth
110mm
External Length / Height
75mm
External
RoHS Compliant
External Width
45mm
Rohs Compliant
Yes
Signal Conditioner Input
0.1Hz To 120kHz
11.2
100240_en_05
Displaying the Switching Output
Setting the filter depth of the analog output
when using frequencies as input value (setting
range 1...15).
This function can only be configured using
the membrane keyboard.
Setting the analog output value
if the measuring range is fallen below
(setting range 0.00…24.00 mA, or
0.00…12.00 V)
Setting the analog output value
if the measuring range is exceeded
(setting range 0.00…24.00 mA, or
0.00…12.00 V)
Setting the analog output value with wire break
or an input signal that is not available
(setting range 0.00…24.00 mA, or
0.00…12.00 V)
Saving. By pressing the
parameters are saved.
By pressing the
terrupted without saving the parameters set.
By pressing the
overwritten by the default values. The parame-
ters of the frequency input and analog input are
unaffected.
If "High Setpoint" is exceeded, the transistor
switches to "High",
If "Low Setpoint" is fallen below, it switches to
"Low" (with hysteresis).
If"High Setpoint" is exceeded, the transistor
switches to "Low",
If "Low Setpoint" is fallen below, it switches to
"High" (with hysteresis)
If "High Setpoint" is fallen below, the transistor
switches to "High".
If "High Setpoint" is exceeded, the transistor
switches to "High".
Transistor is permanently switched (N/C).
Transistor is permanently switched off (N/O).
Between "Low Setpoint" and "High Setpoint",
the transistor switches to "High".
If "Low Setpoint" is fallen below, and
"High Setpoint" is exceeded, the transistor
switches to "High".
-key, the current settings are
key, the setting mode is in-
key, the set
11.3
11.4
Messages in Operating Mode
Menu Guidance
Has fallen below the measuring range.
This message and the current frequency flash
alternately if the frequency falls below the bot-
tom measuring range set.
Measuring range exceeded.
This message and the current frequency flash
alternately if the frequency exceeds the top
measuring range set.
No input signal.
This message flashes for the following reasons:
1. No sensor connected!
2. For NAMUR: a) Short-circuit or b) Wire-
3. Short-circuit frequency <-> GND!
4. No input signal found within the wire-break
detection time set
In edit mode, the arrow points to the function to
be set.
Input
Zero
break!
Full Scale
Input
Analog
Output
Output
Digital
Setpoint
Low
(l.br.time).
Setpoint
High
PHOENIX CONTACT
MCR-f-UI-DC
10