MCR-F-UI-DC

Manufacturer Part Number
MCR-F-UI-DC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-F-UI-DC

Input Type
0.1 Hz To 120 KHz
Output Type
Analogue Voltage Or Current
No. Of Output Channels
2
Accuracy
± 0.15%
Approval Bodies
UL Recognised
External Depth
110mm
External Length / Height
75mm
External
RoHS Compliant
External Width
45mm
Rohs Compliant
Yes
Signal Conditioner Input
0.1Hz To 120kHz
10
Figure 4
10.1
100240_en_05
+
+
+
+
Functions of the Membrane
Keypad
Special Function of the Keys in Edit Mode
Press the key briefly: The output value calcu-
lated is displayed.
By pressing the key again, you return to the cur-
rent input measured value.
Press the key briefly (< 0.sec.): Switches the
module to edit mode for frequency input sig-
nals.
Press the key for at least 2 seconds: Switches
the module to edit mode for analog input sig-
nals.
Press the keys briefly together (< 0.5 sec.):
Switches the module to extended edit mode
Press the keys briefly together: Ends edit
mode, without saving any settings that may
have been made.
Adopts the current setting in edit mode and
switches automatically to the next value.
In edit mode for pulse input signals and for ana-
log input signals, pressing the enter key
addition to the
or backward counting.
By releasing the key and then briefly pressing it
again, it is possible to carry out fine adjust-
ments.
Membrane keypad
or
key accelerates forward
in
11
11.1
Display on LCD
Display Within Setting Range
Frequency input for NAMUR, 2, 3 and 4-wire
sensors, incremental encoders with push-pull
and HTL output signal and dry contact. Settings
can be made in either Hz or RPM/kRPM [Dis-
play: kRM] / MRPM [Display: MRM].
Frequency input for NAMUR sensors with wire
break and short-circuit recognition. Settings
can be made in either Hz/kHz or RPM/kRPM
[Display: kRM] / MRPM [Display: MRM].
Current input 0…20 mA
Voltage input 0…10 V
ON delay of switching output.
(setting range 0…30 sec., default value = 0.00
sec.)
OFF delay of switching output.
(setting range 0…30 sec., default value = 0.00
sec.)
Setting POWER ON delay (switching output)
(setting range 0…30 sec., default value = 1.00
sec.) During this period, the switching output
does not react to events. This function is only of
effect directly after switching on the supply volt-
age.
Setting the wire-break detection time
(setting range 0.2…10.1 sec., default value =
10.1 sec.)
If no input signal is detected during this period,
"No Input" appears on the display and the out-
puts behave according to their settings
Setting the end value
(setting range 75…125%, default value =
100%)
Setting the zero point in relation to the previ-
ously set
output signal: (setting range -5…+5 mA / -
2.5…+2.5 V;
default value = 0 mA / 0 V)
Setting the division factor from 0.1 to 9999 (de-
fault value = 1.0). Slow positioning tasks require
holed coupling halves with multiple divisions
(factor > 1). Measuring the rotational speed of a
motor at the gearbox requires a small division
factor (factor < 1).
PHOENIX CONTACT
MCR-f-UI-DC
9