Note A delay in network transmission time will occur from the time the Hold Flag
■ Example of Bottom Hold
5. For offset compensation, set the offset value in the Scaling Offset field.
6. Return to the General Tab, click the Download Button, and then click the
7. Click the OK Button and exit the window.
Peak/bottom hold is used to hold the maximum (peak) value or minimum (bot-
tom) value of the analog input value. When the Hold Flag (output) allocated in
the OUT Area turns ON, the hold function starts, searching for the peak or
bottom value until the Hold Flag turns OFF. (The peak/bottom value is
refreshed when the Hold Flag turns OFF.) The comparator function can be
used to compare the peak or bottom values allocated as analog data. (Refer
to details on the comparator function.)
turns ON (or OFF) in the Master’s ladder program until notification of the flag’s
status is actually sent to the Slave. Therefore, even when the Hold Flag is ON,
the first analog data transmitted to the Master when the CPU Unit power is
turned ON may be the data from when the Hold Flag was OFF. To collect
peak/bottom hold data using the Hold Flag at the Master, configure a ladder
Previous value
Hold value
Also select either Default Scaling or User Scaling in the Scaling Type
field.
Reset Button to reset the Unit.
Hold Flag
Hold function starts
ON
Bottom hold value
Analog input value
Hold function stops
The bottom value
will be updated.
OFF
Section 7-4
341