DRT2-MD32B Omron, DRT2-MD32B Datasheet - Page 426

no-image

DRT2-MD32B

Manufacturer Part Number
DRT2-MD32B
Description
16In,16Out Horiz MIL Conn NPN
Manufacturer
Omron
Datasheet

Specifications of DRT2-MD32B

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Hold Flags (Output)
(Instance 190)
Temperature Input Terminals
Note A delay may occur between when the Master’s power is turned ON until notifi-
The following format is used when this data pattern is allocated, starting from
the rightmost byte of the Master
Hold Flags are used with the peak/bottom hold and top/valley hold functions.
The Hold Flags are used to control the hold execution timing from the Master
and are allocated in the Master using the following data format (1 byte).
cation of the Hold Flag status is sent to the Slave.
The details for each bit are shown in the following table.
The following format is used when the Hold Flags are allocated, starting from
the rightmost byte of the Master
+0
Word 15
Bit
0
1
2
3
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Bit 7
Abbreviation
Word 15
HD0
HD1
HD2
HD3
+0
Bit 6
Hold Flag for
Input 0
Hold Flag for
Input 1
Hold Flag for
Input 2
Hold Flag for
Input 3
Bit 5
Top Detection
Timing Flags
Temperature Data 1 for Input 0
Temperature Data 1 for Input 0
Temperature Data 1 for Input 1
Temperature Data 1 for Input 1
Temperature Data 1 for Input 2
Temperature Data 1 for Input 2
Temperature Data 1 for Input 3
Temperature Data 1 for Input 3
Name
.
.
Bit 4
8 7
The hold function is performed for Tem-
perature Input 0 while this flag is ON.
The hold function stops and the last
value is held when the flag goes OFF.
The hold function is performed for Tem-
perature Input 1 while this flag is ON.
The hold function stops and the last
value is held when the flag goes OFF.
The hold function is performed for Tem-
perature Input 2 while this flag is ON.
The hold function stops and the last
value is held when the flag goes OFF.
The hold function is performed for Tem-
perature Input 3 while this flag is ON.
The hold function stops and the last
value is held when the flag goes OFF.
Bit 3
HD3
8
7
Generic Status Flags
Bit 2
HD2
Details
Hold Flags
Valley Detection
Bit 1
HD1
Section 7-6
Timing Flags
Bit 0
HD0
405
0
0

Related parts for DRT2-MD32B