Checking the Wiring and Making Adjustments
432
1,2,3...
Adjusting the DRT2-TS04T’s Upper and Lower Limit Values
Input Terminal Connections
1. Open the thermocouple leads from the ZERO-CON (0 ° C bath).
2. Check the sensor and input type being used.
3. Connect the Configurator to the DeviceNet network and go online.
4. Upload settings to the Configurator.
5. Turn ON the power supplies of all Units, including the Temperature Input
6. Double-click the icon of the Temperature Input Terminal to be set in the
NC
DMM
NC
Note When using an R, S, B, E, or W sensor, use a K thermocouple’s com-
Terminal to be adjusted. Wait approximately 30 minutes for the Tempera-
ture Input Terminal’s internal temperature to stabilize.
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
IN0
IN0
+
pensating conductors. In addition, when using an R, S, or B type sen-
sor, set the input type as K2 (0.0 to 500.0 ° C). When using an E or W
type sensor, set the input type as K1 (–200 to 1,300 ° C).
NC
STV
NC
IN1
IN1
+
INPUT
Compensating
conductors
NC
Cold junction compensator
ZERO-CON
NC
0°C/32°F
IN 2
IN 2
+
(0 ° C bath)
NC
NC
IN3
OUTPUT
IN3
+
Open when adjusting upper/lower limit.
Short when adjusting bias compensation.
Section 7-6