Analog Input Terminals
Cumulative Counter
Setting Using the DeviceNet Configurator
354
1,2,3...
Note The following table shows the divisions for the cumulative counter.
9. Click the OK Button and exit the window.
The cumulative counter calculates an approximation to the integral of analog
input values over time. The cumulated value can be calculated in “count
hours” (by selecting “hours”) or “count minutes” (by selecting “minutes”). The
count value is the analog input value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
input value of 100 counts continuing for one hour. The counter range for a
four-byte area (two words) for count hours or count minutes is –214,748,364.8
to +214,748,364.7. Data is displayed on the Configurator in units of 0.1 hour
or minute.
Monitor values can also be set in the Unit. When the cumulated count value
exceeds the set monitor value, the Cumulative Counter Flag in the area for
Generic Status Flags turns ON.
DRT2-AD04
DRT2-AD04H
1. Double-click the icon of the Analog Slave to be set in the Main Window and
Analog input value
Hour
Minute
Hour
Minute
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
Unit
Unit
Division width
3.6 s (1/1,000 hour)
60 ms (1/1,000 minute)
15 s (1/240 hour)
250 ms (1/240 minute)
Divisions
Divisions
Cumulated value (count x
hour or count x minute)
Time
Section 7-4