SYSMAC LINK Units must be inspected on a regular basis to ensure correct
operation. SYSMAC LINK Units are built primarily of solid-state components
and contain almost no parts subject to wear. Nevertheless, the life span of
some solid-state components can be shortened as a result of adverse envi-
ronmental conditions.
We recommend that the following points be checked at least once every 6 to
12 months as part of a standard inspection program. Ambient conditions
should be checked more frequently. If any of these items deviate from the
prescribed standards, take appropriate action to correct the condition.
We recommend that users have backup Units available to make repairs and
minimize down-time if a problem occurs in a SYSMAC LINK Unit.
Please observe the following precautions in the event of a problem:
• Always turn the power off when replacing a SYSMAC LINK Unit.
• After replacing a Unit, always make the required settings before restarting
• If a SYSMAC LINK Unit fails, replace it with a new one and immediately verify
• When returning a malfunctioning SYSMAC LINK Unit for repair, please attach
• If you suspect that a poor connection is the cause of a malfunction, clean the
The C200HW-SLK13/14/23/24 SYSMAC LINK Units’ functions are equal to or
superior to those of the C200HS-SLK12/22 Units, so C200HS-SLK12/22 Units
can be replaced with C200HW-SLK13/14/23/24 Units. Do not replace C200HW-
SLK13/14/23/24 Units with C200HS-SLK12/22 Units.
The following tools and equipment will be needed to perform inspection and
adjustments.
• Assorted flat-blade and Phillips screwdrivers
• Circuit tester or digital VOM
• Industrial-grade alcohol and clean cotton cloth
• Synchroscope
• Pen-chart recording oscilloscope
• Thermometer, hygrometer
Ambient conditions
Installation
operation.
that the new Unit is working properly.
a detailed description of the problem to the Unit and return it to the sales office
nearest you (see listing at the end of this manual).
connectors using a clean, soft cloth and industrial-grade alcohol. Remove any
lint or threads left from the cloth, and re-mount the SYSMAC LINK Unit.
Item
Temperature: 0° to 55°C
Humidity: 10% to 90% (no condensation)
Dust-free
SYSMAC LINK Units securely attached?
Cable connectors tight?
Screws tightened on terminal blocks for external wiring?
Cabling used for external wiring intact (no breaks)?
Description
Section 9-1