3-2-2 Installation and Wiring
C1000H/C2000H
Mounting Position
22
Note
The following table shows which power cables are included with the
C1000H-APS01 and C200H-APS03 as accessories.
When connecting 2 SYSMAC LINK Units to an Auxiliary Power Supply Unit,
order the following cables separately as required.
The backup function will be disabled when the PC’s power is off, so connect
the power supply terminals to an AC power supply other than the one con-
nected to the PC.
Always supply power to the Power Supply Unit before supplying power to the
PC.
The C1000H-APS01 can be mounted in any slot, but the power cables are rela-
tively short, so the Power Supply Unit cannot be more than 2 slots from the SYS-
MAC LINK Unit. One Power Supply Unit can supply backup power to two SYS-
MAC LINK Units, as shown below.
C1000H-APS01
C200H-APS03
C1000H-APS01
C200H-APS03
P/S
Name
1. Turn off the power supply to the PC before mounting the Power Supply Unit.
2. Firmly tighten the Backplane mounting screws for the Power Supply Unit.
3. Leave the protective sticker in place on the Unit when wiring to prevent clip-
4. Remove the protective sticker after completion of wiring before turning on
5. Do not pull on the cable. Pulling on the cable could break wires inside.
6. Do not bend the cable past the minimum radius. Bending the cable too far
pings and other foreign matter from entering the Unit during the wiring pro-
cedure.
power to the Unit. If Unit is operated with the protective sticker in place, the
Unit may overheat, causing operational errors.
could break wires inside.
APS SLK SLK
Unit
Unit
Green
Indicator
Color
Condition
Lit
Not lit
C1000H-CN111
C200H-CN111
C1000H-CN111
C200H-CN211
Power cable
Power cable
CPU PS
Power is being supplied to the SYSMAC LINK Unit.
Power is not being supplied to the SYSMAC LINK
Unit.
1 cable provided
1 cable provided (for 1 SYSMAC LINK Unit)
Same as the one provided with the Unit.
For connection to 2 SYSMAC LINK Units
Meaning
Notes
Notes
Section 3-2