Replacing SYSMAC LINK Units
9-2
Manually Set Data Link
Network Parameters
Replacing SYSMAC LINK Units
1, 2, 3...
Note
Note *Refer to 4-5 Polling Unit Setting for more information on the polling unit.
If data links have been established manually, the data link table must be re-set
after mounting the new Unit and before activating data links. If data link areas are
set automatically, this re-set operation is unnecessary as long as SW1 and SW2
are set correctly.
To use network parameters other than default values, use the following proce-
dure after mounting the new Unit.
1. Data link tables and network parameters are stored in the EEPROM in the
2. Always turn off the power supply to the PC before attempting to replace a
1. Set SW1 pin 8 to ON (polling unit setting*).
2. After initializing the SYSMAC LINK Unit, confirm that it has correctly joined
3. Set SW1 pin 8 to OFF (polled unit setting*).
4. After initializing the SYSMAC LINK Unit, confirm that it has correctly joined
SYSMAC LINK Unit. Be extremely careful when removing this component
from the old SYSMAC LINK Unit and inserting it in the new Unit.
Unit.
the Network by checking the indicators (INS LED lit, and ERC and ERH
LEDs not lit indicate normal operation).
the Network by checking the indicators (INS LED lit, and ERC and ERH
LEDs not lit indicate normal operation).