NT20S-KBA01 Omron, NT20S-KBA01 Datasheet - Page 27

CHEM RESISTANT CVR FOR NT21

NT20S-KBA01

Manufacturer Part Number
NT20S-KBA01
Description
CHEM RESISTANT CVR FOR NT21
Manufacturer
Omron
Datasheets

Specifications of NT20S-KBA01

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
1-3-2
System Configuration
this handshaking connection established,
It is extremely important that you have
COM06
RS-422
or communication will not exist.
DM6655 = 5700
DM Setting to set
NT Link (1:N) Systems
C200HX Setup
Com 06 Port A
for 1:N NT Link
Reference: When connecting the C200HX/HG/HE and an RS-232C/RS-422 converter unit,
Cable 1
RS-422
e.g. 1= 2 PT Nodes
System will not
accept a 0 (zero).
PLEASE NOTE:
The second digit
signifies the max. #
of PT Nodes for 1:N
NT Link.
When NT20S is connected to a PC in a 1:N connection, use an RS-232C cable and
RS-422/485 cables.
use a converter unit whose lot number is 15Y5 or later. Converter units of lot num-
bers previous to 15Y5 cannot be connected.
NT-AL001
7= 8 PT Nodes
NT-AL001
RS-232
Cable 2
RS-232
NT-AL001
RS-422
Dipswitch settings:
1 & 6 are ON.
Everything else is OFF.
NT20S Setup
1:N NT Link
Cable 3
RS-422
Unit #0
NT-AL001
NT-AL001
RS-422
RS-232
NT20S
Cable 2
RS-232
Dipswitch settings:
1 & 6 are ON.
2 is ON - only if this is the last AL001 unit
Everything else is OFF.
NT20S Setup
1:N NT Link
Unit #1
NT-AL001
RS-422
Section 1-3
11

Related parts for NT20S-KBA01