Example of Display Screen Switching
Overview of Direct Connection Operations
S Continuous screens and overlapping screens
This example operates the PC switch (bit) to switch the NT20S display screen.
S Support tool settings
S PC ladder program
S Program operation
(1) Screen #2 is displayed on the NT20S when bit 00002 turns ON.
(2) Screen #3 is displayed on the NT20S when bit 00003 turns ON.
(3) When the screen switch strobe flag turns ON, the number of the currently dis-
Screen switch strobe flag
Continuous or overlapping screens can be displayed by designating the parent
screen. If a child screen is designated, only the child screen is displayed.
For the continuous and overlapping screens, refer to the “Classification of
Screens” (page 122).
Make the following settings with the support tool:
PT status control area:
PT status notify area:
Screen number to be created: Screen #2 and #3
Create a PC ladder program as follows:
00002
11212
00003
played screen is read and written to the currently displayed screen word in the
PT status notify area. In this case, the NT20S will not write the same screen
twice.
@MOV(21)
@MOV(21)
@MOV(21)
#0002
#0003
100
110
100
100
Word 0100
Word 0110
Screen number
Screen switch setting word
Screen number
Screen switch setting word
Screen number
Screen switch setting word