Setting the Conditions of Communications with the PC/Host with Memory Switches
Selecting the Host Link Communication Speed
(NT20S-ST121-EV3 only)
When using the NT20S-ST121-EV3 with the host link, the baud rate of the com-
munications with the PC can be set. Use the “Baud Rate” switch and select 9600
bps or 19200 bps.
The factory setting has been made at 9600 bps.
Select the baud rate of the communication with the PC by the menu operation from
the System Menu as mentioned below.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without set-
ting, press [Quit].
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
Automatic Reset
Baud Rate
MEMORY SW MENU
MEMORY SW MENU
Host Link
OFF
OFF
None
NT20M
No
9600bps
DIP-SW Status
(1/2)
(2/2)
WRT&
WRT&
Page
Page
EXIT
EXIT
Quit
Quit
Select “Maintenance Mode”.
Select “Memory Switch”.
Select “Page”.
If the host link is not selected,
press the “Comm. Type” touch
switch and select “Host link”.
Each time the “Baud Rate”
touch switch is pressed, the set-
ting option alternates between
“9600 bps” and “19200 bps”.