Writing Programs
Trial Operation
Preparations for Trial Operation
Note Although the Programming Device is connected to the Duplex Unit, writing is
When registration in the I/O table has been finished, make sure that the I/O
words allocated to each Unit match the addresses used in the user program.
Create the ladder program using a Programming Device and transfer the data to
the CVM1D.
performed for the active CPU Unit. By pressing the INIT switch, the same pro-
gram or data can be written to the standby CPU Unit in simplex mode.
When all the startup preparations have been completed, start trial operation.
Turn OFF the power once and perform the following before starting.
• Detach the output wires so that the system will not be affected by any faulty
• Short-circuit the START INPUT on each of the two Power Supply Units for the
• If a Communications Unit is mounted, provide appropriate measures to pre-
operation.
CPU Units.
vent any influence on other systems.
Section
4-4
91