3-7-2 Input Units
Wiring I/O Units
Voltage output
+
Output
0 V
Incorrect
Sensor
power
supply
The terminal block of an I/O Unit can be removed by loosening the mounting
screws. You do not have to remove the lead wires from the terminal block in or-
der to remove the block from an I/O Unit.
Do not wire voltage inputs as shown on the left below.
When two-wire sensors, such as photoelectric sensors, proximity sensors or
limit switches with indicators are connected to the PC as input devices, the input
bit may be turned ON erroneously by leakage current. In order to prevent this,
connect a bleeder resistor across the input to reduce the input impedance.
2. Use reinforced insulation or double insulation on the DC power supply con-
3. Use separate power supplies for Relay Output Units and DC I/O Units when
Sensor
nected to DC I/O Units when complying with EC directives (low voltage).
complying with EC directives (low voltage).
IN DC input
COM ( - )
Terminal block mounting screws
Loosen the terminal block mounting screws to remove
the terminal block from the I/O Unit. Make sure the
mounting screws on the terminal block are tightened af-
ter wiring is complete and the terminal block is re-
mounted to the I/O Unit.
Voltage output
Input
power
supply
+
Output
0 V
Bleeder
resistor
Correct
Sensor
power
supply
R
COM (+)
IN DC input
Section
PC
3-7
73