3-3
3-3-1 Racks
52
Installation
Installation
Do not mount the PC in a control panel in which high-power equipment is in-
stalled and make sure the point of installation is at least 200 mm away from pow-
er lines as shown in the following diagram. Ensure the plate to which the PC is
mounted is grounded.
When using more than 10 meters of I/O connecting cable, use connecting power
lines of at least 2 mm
Every Rack must be mounted vertically, that is, with the printing on the front pan-
els oriented as it would normally read. Racks may be directly mounted to any
sturdy support meeting the environmental specifications.
Whenever possible, use wiring conduits to hold the I/O wiring. Standard wiring
conduit should be used, and it should be long enough to completely contain the
I/O wiring and keep it separated from other cables.
The duct work shown in the following diagrams is not used for mounting the
Racks. Although optional, this duct work can be used to house the wires from the
I/O Units that run along the sides of the Racks, keeping the wires from becoming
entangled. The following diagram illustrate the correct way to mount the Racks.
Power lines
200 mm min.
PC
200 mm min.
2
between control panels mounted to Racks.
Section
3-3